300 °C oil temperature control unit instead of a 700-litre thermal oil boiler
In the heat exchanger of a filter system, a 72 kW MARSE SMART 6 PLUS A300TS temperature control unit replaces a 700-litre thermal oil boiler. The installation now works with about 100 litres of oil, starts up on its own by timer and controls both heating and cooling.
- Equipment
- SMART 6 PLUSoil up to 300 °C
- Power
- 72 kWheating
- Pump
- 200 l/minpump flow rate
- Oil
- 700 l → ≈ 100 lin the whole installation

The case at a glance
- Equipment
- MARSE SMART 6 PLUS A300TS temperature control unit, thermal oil from 30 to 300 °C.
- Replaces
- A thermal oil boiler with 700 litres of fluid.
- Oil in the circuit
- ≈ 100 litres, including the unit, the piping and the heat exchanger.
- Start-up
- Automatic, with the timer function: no operator needed.
- Unit data
- 72 kW heating, 200 l/min pump at 8 bar, 120–230 kW cooling.
The process and the initial problem
The filter system needs its heat exchanger to work at a stable temperature. Until now, that heat was supplied by a thermal oil boiler with 700 litres of fluid: a large volume that had to be heated completely before the heat exchanger received its first useful calorie.
From a process point of view, a boiler of this size has three drawbacks: a lot of thermal inertia (it is slow to reach the setpoint and to respond to changes), it can only heat (it cannot remove heat if the process needs it) and it depends on an operator to start it up. From a maintenance point of view, 700 litres of hot oil mean a higher fire load in the plant, more fluid to top up and more time at each oil change.
Before and after
Heat only the oil that circulates, instead of keeping a 700-litre boiler hot.
- Boiler with 700 litres of oil
- An operator had to go and start it up
- Lots of space and lots of hot oil to handle
- SMART 6 PLUS connected directly to the heat exchanger
- About 100 litres of oil in the whole installation
- Automatic start-up with the timer function
How much inertia weighs: an indicative calculation
To raise the oil temperature by 100 °C, without counting losses or the metal mass:
Theoretical estimate with thermal oil of density 0.87 kg/l and specific heat 2.1 kJ/kg·K. It does not replace an on-site measurement.
Why a MARSE temperature control unit in this case
For the process engineer
- Heating and cooling PID control with auto-tuning: the heat exchanger temperature stays stable, without the swings of an on/off boiler.
- Programmed heating and cooling ramps: the heat exchanger suffers no thermal shock.
- Cooling capacity (120–230 kW): if the process adds heat, the unit removes it. A boiler cannot.
- Real-time graphs of temperature, pressure and flow to document every start-up.
For the maintenance manager
- About 100 litres of oil instead of 700: less fluid to buy, store, change and manage as waste.
- Magnetic pump without mechanical seal, standard at MARSE from 140 °C: no more of the most common leak point of a hot oil pump.
- Timer start-up: the unit is at temperature when the shift begins, without anyone having to go and switch the boiler on.
- Alarms on a 7″ touch screen and a single compact, accessible unit with standard MARSE spare parts.
Technical keys
- Less volume, less inertiaWith about 100 litres in the circuit, the oil reaches the setpoint in minutes and responds quickly to changes.
- Heating and cooling in a single unitThe SMART 6 PLUS heats with 72 kW and cools with its 120–230 kW heat exchanger.
- SecuritySeven times less hot oil in the plant and a closed circuit with a magnetic pump.
- AutonomyThe timer starts the unit at the programmed time; the alarms warn of any deviation.
Result
Frequently asked questions
Can a temperature control unit replace a thermal oil boiler?
Yes, when the power and temperature allow it. In this case a 72 kW SMART 6 PLUS A300TS, rated up to 300 °C, replaces a 700-litre boiler by heating the filter system's heat exchanger directly, and it can also cool, something the boiler could not do.
How much oil does the installation need with the temperature control unit?
About 100 litres in total, including the unit, the piping and the heat exchanger, compared with the 700 litres of the previous boiler.
How does the unit start up without an operator?
With the temperature control unit's timer function: the start-up time is programmed and the unit reaches temperature before the process begins.
What are the advantages for maintenance?
Less oil to top up and manage, a magnetic pump without mechanical seal from 140 °C, on-screen alarms and a single compact unit with standard spare parts.